50-74-201. State boiler inspectors.
The department shall appoint state inspectors of boilers and shall prescribe their duties and term of office and fix their compensation.
Use Open PDF for a printable PDF in a new tab.
The department shall appoint state inspectors of boilers and shall prescribe their duties and term of office and fix their compensation.
(1) In addition to the state boiler inspectors, the department shall issue to the inspectors of boiler insurance companies authorized to do business in the state commissions, certificates, or other recognition as special boiler inspectors and may accept the inspection reports of such special inspectors as equivalent to those of the state inspectors.
(2) Each such special inspector shall hold a certificate as boiler inspector issued by the national board of boiler and pressure vessels inspectors.
(3) Such special inspectors shall receive no salary or expenses from the state, nor shall the state collect inspection fees for inspections made by such special inspectors.
In making an inspection of the boilers and machinery herein provided for, the inspectors may act jointly or separately, but the inspector or assistant inspector making such inspection must in all cases certify the same under the seal of the inspector of boilers and safety.
(1) Any person purchasing any boiler, whether traction or stationary, shall be entitled to receive from the seller the certificates of inspection issued on such boiler.
(2) Any person failing to comply with the provisions of this section shall be deemed guilty of a misdemeanor.
(1) The inspector of boilers must inspect all boilers and steam generators before the same are used.
(2) All persons who bring into this state for operation in this state any boiler or boilers must notify the department stating the number and kind of boilers and where they are to be located and operated in this state and must secure from the department a certificate of inspection before boilers are placed in operation except in the case of new boilers, which must be inspected within 90 days after they are put in use.
Any owner, operator, or user who opens a boiler or boilers between inspections for repair or other reasons must notify the department of such action, and such boiler or boilers shall at the discretion of the department be inspected by the state or special boiler inspector before the boiler or boilers may be placed back in operation.
Any person failing to give notice to the department as provided in 50-74-206 or 50-74-207 or who operates such boilers without a certificate from the department shall be punished by a fine of not less than $100 or more than $500 for each offense, by imprisonment in the county jail for not less than 30 or more than 90 days, or by both such fine and imprisonment.
(1) (a) All manually fired boilers and all boilers and banks of boilers rated with a total input of 400,000 Btu's an hour or greater must be inspected at least once each year.
(b) All automatically fired boilers rated with an input of less than 400,000 Btu's an hour must be inspected at least once every 2 years, except that an automatically fired boiler in a school, day-care center, hospital, rest home, retirement center, or place of assembly with a capacity for more than 100 persons must be inspected once a year.
(c) Boilers exempt under the provisions of 50-74-103 do not require inspections.
(d) Upon written application, longer inspection intervals may be authorized by the department.
(2) In addition to the inspection required by subsection (1), it is the duty of each inspector to examine at proper times, when in the inspector's opinion an examination is necessary, all boilers that have become unsafe from any cause and to notify the owner or the person using the boilers of any defect and what repairs are necessary to render them safe.
(3) If a boiler is found, upon inspection, to violate safety standards set forth in rules referred to in 50-74-101, the department shall order the owner of the boiler to comply with the standards. An owner who negligently or knowingly fails to comply with an order is guilty of a misdemeanor and upon conviction is punishable by a fine of not less than $50 or more than $100, imprisonment for not more than 60 days in a county detention center, or both.
(4) The department may accept valid inspections for traction engines that have been performed by other states.
It is the duty of the owners, engineers, or managers of steam or water boilers to allow the inspector free access to the same.
In case the owner, operators, or manager of any boiler is notified by the inspector to have the boiler ready for inspection on a certain day and fails to have such boiler ready for inspection at such time, the inspector shall notify the department to gain access to the boiler.
The owner, engineer, or manager of any boiler who has refused access resulting in a department order must pay all transportation and hotel expenses of the inspector who makes the inspection directed by such order in addition to the inspection fee provided by law.
Any person failing to immediately comply with department directed access to the boiler shall be deemed guilty of a misdemeanor and upon conviction thereof shall be punished by a fine of not less than $100 or more than $500, by imprisonment in the county jail for not less than 2 months or more than 6 months, or by both such fine and imprisonment.
It is the duty of the engineer operating any boiler or boilers to assist the inspectors in their examination of the boilers and point out any defects known to the engineer in the boilers or machinery under the engineer's charge. If an engineer does not comply with this section, the engineer's license must be revoked or suspended.
(1) The inspector must be satisfied by a thorough interior and exterior examination that the:
(a) boilers are well-made and of good and suitable material;
(b) openings for the passage of water and steam, respectively, and all pipes and tubes exposed to heat are of the proper dimensions and free from obstructions;
(c) flues are circular in shape;
(d) fire line of the furnace is at least 2 inches below prescribed minimum waterline of the boilers;
(e) arrangements for delivering the feed water are such that the boilers cannot be injured by the feed water; and
(f) boilers and the steam connections may be safely employed without danger to life.
(2) A boiler or steam pipe or any of the connections to a boiler or steam pipe that are made in whole or in part of bad material or are unsafe from any cause may not be approved. Nothing in this section may be construed to prevent the use of any boiler or steam generator, that is not constructed of riveted iron or steel plates, when the inspector has satisfactory evidence that the boiler or steam generator is equal in strength to and as safe from explosion as boilers of the best quality, constructed of iron or steel plates.
When necessary, the boiler inspector shall subject boilers, except those exempted by 50-74-103, to hydrostatic pressure, which hydrostatic pressure shall not exceed 150% of the steam pressure allowed on the boilers, providing there are no such leaks on such boilers which prevent the inspector from applying such hydrostatic pressure.
The inspector must be satisfied that:
(1) the safety valves are of suitable relieving capacity ratings, sufficient in number and area, and properly arranged and properly adjusted so as not to allow a greater pressure in a boiler than the amount prescribed by the inspection certificate;
(2) there are a sufficient number of gauge cocks properly inserted to indicate the amount of water and suitable gauges that will correctly record the pressure of steam; and
(3) adequate and certain provisions for an ample supply of water to feed the boiler at all times and suitable means for blowing out are provided so as to thoroughly remove mud and sediment from all parts of the boiler when it is under pressure of steam.
(1) If a boiler is constructed with lap horizontal seams on the boiler, dome, or drum, a factor of 4 1/2 must be used in determining the safe working pressure allowed on the boiler.
(2) If a boiler is constructed with butt strap horizontal seams, a factor of four may be used in determining the safe working pressure.
(3) If a boiler is a historical boiler, as defined by the department by rule, on stayed sections, a safety factor of four must be used in determining the safe working pressure.
(4) If a boiler rests on a side wall on lugs, is hung by I-beams, or is in any way set up so that the weight of the boiler is pulling against the horizontal seam of rivets, a factor of five must be used in determining the safe working pressure.
(5) If the horizontal lap seams of a boiler are exposed to the fire, a factor of five must be used in determining the safe working pressure.
(6) On new stay bolts, 7,500 pounds pressure per square inch is allowed. If the stay bolts are corroded or defective, the inspector must determine the pressure to be allowed on the stay bolts.
(7) On braces made of solid material, 8,000 pounds pressure per square inch is allowed. On welded braces or braces with only one crowfoot, 6,000 pounds pressure per square inch is allowed.
(8) Cast iron may not be used in the construction or reinforcements of a boiler if the pressure allowed on the boiler is more than 100 pounds per square inch.